Monday, December 19, 2016

Has Recent Work Introduced Errors?

You may have read this analysis of the errors DBDOC found that had been introduced into a client system over four years.

Here is another summary analysis of the important errors introduced into a different system over five years. DBDOC makes this sort of analysis trivial if you have backups of systems before and after work is done. Here are questions that should be asked:
  1. How many errors that could hurt the plant are acceptable?
  2. Why were these errors not in front of the DCS team for evaluation?
  3. How could these errors, all breaking the rules, yield a clean Composer compile?
  4. Should Composer have caught them?

Duplicate ADAPT Blocks and Multiple TSTALM Blocks

There are ten errors that result from the failure of Composer to force a cloned ADAPT or TSTALM block to have S2 or S1 set to -1 when the block is cloned.


Two of these errors are shown below. It is absolutely clear that S2 of block 1060 and S1 of block 1066 both should be 1062, not 2450. The value 2450 is residual from the working logic that was cloned into this logic. This is typical of a class of error made again and again by Composer users.


The block index for the prototype MSDRVR FC 129 Block 1062, centre of a wonderful set of beautiful functioning logic. The highlights show the four extra TSTALM block errors, so there are six of each. Not one of the errors was found when the work was done, compiled by Composer or loaded by the user.

Some Function Blocks are Defaulted as Disabled

This error message shows that one lag function was not enabled when it was added. The effect would show up as inexpicable unintended excursions that are supposed to be smoothed out. Clearly, the default should be to be enabled, not disabled.

Specification out of Range

What does this block do?
We could guess. Why should we have to? Why is this not an error in Composer, as the only legal values are 0, 1 or 2?

TSTQ Tests Block With No Quality

The work being analyzed has only two errors where a block is being tested for quality when it does not have quality to test. Only two!

First, note how the blocks with quality, shown by DBDOC as blue lines, lose that attribute when they go through logic blocks. Here, the cost of the one second lag function is the loss of quality for the pressure signal.

So, bad quality on the pressure signal will not be detected. What is it supposed to do? Simply put the FLOW CONTROL STATION into Manual. Oops!

Summary

There are fourteen potentially significant errors documented here, with many more less severe not mentioned. They should not have been made, and they should have been caught.

Tuesday, September 27, 2016

A System Without DBDOC - Analysis I

This is the first of a series summarizing the severe errors found by DBDOC at INFI 90 sites that do not have our product for system integrity protection. Be assured that there are more errors in this system than the ones shown here, but this article highlights some of the glaring ones. The system has 5723 configuration sheets at a large power plant. This site gets no warning from its existing tools about the errors described below!  DBDOC, however, would be able to alert it to all of them.

Adapt Block Cloning Errors

There are two adapt block cloning errors, caused by failure to change S2 to match cloned logic. Two subsystems are not adapted, even though they look like they are.

[S2 of block 6115 should be 6116, not 5116]        [S2 of block 7814 should be 7815, not 1115]

TSTALM Cloning Errors

There are nine multiple TSTALM situations. Every one of these comes from S1 not being changed when logic was cloned. Fourteen actions can happen mysteriously when they should not, triggered by the prototype logic instead of the new logic. Even worse, fourteen actions do not happen when they should, because the cloned logic is not being tested.
[S1 of block 3130 should be 3122, not 2920]

Why fourteen? One instance was cloned badly six times.


TSTQ Block Inputs Without Quality to Test

There are 209 inputs to TSTQ blocks being tested that do not have quality to test. In addition, quality is being tested on 10 AO/L blocks that do not have quality on their input signal. Three of these flawed tests control the manual interlock of control loops, so the loop will not go into Manual when the quality is bad.
[Analog Transfer block 4307 FC 9 does not have quality to test]

It is disconcerting that a number of the errors flagged look like OR and TSTALM block outputs are being handled incorrectly by being inputs to TSTQ blocks, instead of being OR'd with the outputs.

REDAI Blocks Used Without Being Tested for Quality

There are 46 instances where REDAI blocks can synthesize bad quality, but the value is then used whether or not it is bad. The first one I checked can be bad quality but still control a "FD AIR MASTER" control loop.

The one shown here is kind of cute, if you like scary productions. Good engineering was undone.

[Analog Transfer block 1835 FC 9 does not have quality to impart to the AO/L block and tag]

Function Block Errors

Among the function generator blocks, there are
  • four that change from slope 1:3 to 1:1 instead of clamping
  • four that change from slope 4:1 to 1:1 instead of clamping
  • two that change from slope 7:1 to 1:1 instead of clamping
  • three that with slope 1:1 that also do not clamp
[The large equal value (X,Y) pairs mean that the output rises at the same slope as the input]

Too Few Inputs
One 8 input Qualified OR block has four inputs, but needs seven to trigger it. It ain't gonna happen!

[Qualified OR block 7273 FC 36 will be a 1 if S9 (value 7) of the 4 inputs are value "1"]

Rung Block Errors

Two rung blocks ignore an input without documentation. If a test is in progress, too bad!
[S3 value 20 of FC 111 block 5026 means that value of "TTY TEST IN PROGRESS" is wiped out]

One rung block tests vibration limits, but does not disable the result on bad quality, as designed.

[S6 value 0 of FC 111 block 2606 means that value of  the test quality block is ignored]

Other Errors

There are 29 DAANG and AO/L blocks giving continuous exception reports.

There are 15 DAANG block tags that are designed to show some or all of 2nd and 3rd high and low alarms that will not do that.

One MA Station has type 5, not defined. Another has its initial mode after startup value set to 0, also not defined.

Summary

339 errors are outlined above. This is 339 errors more than the site knows about. What risks do these errors represent to the site? Why do these errors exist undetected? Should this system even be running?


Monday, August 8, 2016

Alarm Management Needs Error Management

Does your system contain alarms that cannot actually ever occur?  Many do.

Alarm management focuses on understanding and controlling the alarms that can be generated in a system.  DBDOC provides techniques for walking through the configuration systematically to validate assumptions and look for problems. Effective alarm management is impossible without error management and configuration analysis.

Here are three example sets of alarms that do not work in a single powerplant configuration:
  1. Intermittent failure caused by duplicated exception report imports
  2. Detected failures to test blocks with quality
  3. Problems that can be found by using DBDOC to walk through the configuration easily
If you do not manage your errors and use the tools DBDOC provides to audit the configuration, you will not be able to manage alarms. Even worse, you can spend a great deal of money fooling yourself about alarms.

Example 1 - Frozen Import Block Error


INFI 90 allows block values from one module to generate "exception reports" when the block value changes status or value. In the case of an analog exception report, the new value is transmitted when it changes by an amount that is specified as "significant".

If a an exception report block value is imported more than once into a module, only one of the import blocks works. The values of any other blocks importing the exception report block value will remain frozen. Furthermore, when an on-line configuration is done, a second import block will silently begin working (!) and the block that was working will freeze at its last value. This applies to both analog and digital exception reports.

DBDOC detects and reports this error. However, when the module is compiled using Composer, the error is not detected.

      Error: Frozen import block [093]

      Duplicate off-module reference (DI/L, DI/L) to Module 1,01,05 Block 1230: 1020324 and
      1020342 [1010536]


The source value above is imported in two places in one module. This instance on a spare block page might have the active connection.


The following shows the intended logic.


There is a 50/50 chance that the correct logic is not working at any time. Simply put, tags 0D0730 "COND RETURN TANK HIGH/LOW LEVEL" and 0D0727 "AUX DEA HIGH/LOW LEVEL" might alarm, but they might not. It is a crap-shoot!

Note: It would seem reasonable to assume that AI/L block 1675, now spare, actually started life feeding S3 of block 1676. The duplicate import situation was discovered and the logic changed properly to get both values of S3 from a single AI/L block somewhere in the past. The problem was that the spare block still can be the active one.

Example 2 - Test Quality of a block that does not have quality to test


Powerplant A has 7707 TSTQ blocks. These four input blocks give a binary [1] as a result if one or more of their inputs have bad quality. Actually, 8592 blocks are being tested in all. Of these, 316 do not have quality to test at all.

Here is one example of an alarm (and shutdown) that will not work, identified by the message here.

       Error: TSTQ tests block with no quality [063]
 
       TSTQ Module 4,05,03 Block 2273 tests Module 4,05,03 Block 6170 (FC 15), which does not
       have quality [4050378]

Obviously, the simple solution to the problem of no alarm on bad quality for 1 GROSS MW TRANSDUCER A is simply to test the quality of the input at IREF P1E0388A instead of the output of the fudge factor sum block 6170.

Example 3 - Misconfiguration of a DAANG Block


DBDOC also allows you to go looking for trouble. Walking through all instances of a Function Code will allow you to look for things that were missed long ago. This example shows bad quality that will not alarm.

DAANG blocks are powerful tools when configured competently. Powerplant A has 6227 of them, the second highest number we have seen in a single plant. I was curious to see how consistently programmed they were. The table shows how a value places on Specification S8 can set bad quality.
This plant uses this extensively. This example shows how the constant 32.0 is applied to S8 with the green highlights. When the raw signal is found by the TSTQ block to be bad quality, the DAANG block will be marked bad quality as intended.
The following example shows that undetected errors exist. The red highlights show that bad quality on this raw input will result in good quality being forced. Oops!
Being interested, I started walking through the 6227 DAANG blocks looking for this particular issue.  I got bored after 200, taking 16 minutes, about 5 seconds per block. I found (and flagged with DBDOC annotations) the following reality:
  • 124 blocks with correct alarm configuration - setting 32.0 into S8
  • 22 blocks incorrectly setting 1.0 into S8
  • 1 block incorrectly setting 0.0 into S8
  • 53 of the first 200 DAANG blocks did not set the quality attribute in this way.

The bottom line is that 12% of the first 200 DAANG blocks (all tagged, by the way) would not alarm on bad quality. I have no reason to think this is not representative, which suggests that perhaps 800 of these tags will not alarm on bad quality in this one system.

By contrast, I checked a system with 7980 DAANG blocks. There were no alarm errors in the first 150 instances, with all quality inputs being generated correctly. At least in this respect, good configuration work would make alarm analysis valid.

In a second system with 5084 DAANG blocks, I found that only 2042 of them used the S8 to set bad quality if needed. In fact, this simple walkthrough with DBDOC showed that that 60% of the blocks I sampled were fed from signals that had no quality to test, but did not reinsert bad quality. That could mean about 2000 simple errors - tag does not show bad quality when it should.

Error and Configuration Management Trump Alarm Management


Alarms cannot be managed if errors prevent them from working. DBDOC can be used to improve alarms both by looking at errors and by walking through the project carefully. Otherwise, any alarm analysis will be incomplete and unacceptable.

Wednesday, August 3, 2016

Output Cusps - Exceptionally Artistic!

We came across the pretty but alarming output forms shown here at a client. The scale is one minute per cusp and just over 1% amplitude. This is important because it means that the HMI and historian would not see this at all. DBDOC Watch Window handles it nicely, as is evident.

So what is going on here?



The blue line is the output of a FC 80 Station block and the output cusps were, in fact, a significant issue. The green line is the raw PV input (nice and smooth). However, the APID block was being fed by an exception-reported version of the PV, shown in red. The significant change specification was 0.1%, so the exception-reported value actually was competently implemented, changing in steps, as expected.

The problem simply is that the APID algorithm used a derivative term. As the two diagrams make painfully obvious, this simply does not work. Although the PV signal is changing at a nice fairly constant rate, the controller, fed by the red step input, is hit with a huge change accumulated over one minute, but seen as happening in 250 ms. Thus, the derivative is calculated as being 240 times bigger than it actually is.






















The second image shows that, if the PV is changing so that the exception reports are triggered by the significant change, the cusps are smaller, as they have a better time base. but they are still misleading and problematic.

The bottom line is that PID and APID algorithms should never use a derivative term if the PV is affected by an exception-reported input PV. It cannot work mathematically, and it sure kicks the process in the teeth, again and again.

DBDOC can't yet detect this error situation automatically, but we are working on it.  Stay tuned.

DBDOC 10.7: Now Detects Unitialized Rung Stacks

We always have our eyes out for new error situations that DBDOC can detect and protect you from.

At a training session recently, we happened to notice a FC 111 rung block with mysterious output [1] (blue). This made no sense, because the logic is OUTPUT = (S13 OR S14 OR S15 OR S16) AND S17, but none of S13-16 are [1] (blue), so the output shouldn't be [1], but it is. We verified the specifications, which matched what the CLD showed.



There are actually two different reported errors on this particular block, as you can see from the presence of two error markers.  There is also an unreported error, which we will describe for completeness.

Rung block spec is wired but unused

The first (reported) error is reported as follows:

Rung block spec is wired but unused [ERROR 124]

Rung block Module 9,25,05 Block 7660 S12 is wired (block 3006) but unused by S2 value 000[92505F2A.CAD]
S2 is the operation that acts on input S12, but S2 is 0, which means ignore the input, and instead use the value from the top of the stack.  It may well be unintentional that S2's value be ignored.

Operation on an unwired input

There is actually another error which is not reported, because it makes no difference to the output:

The specs S2-S11 are operations on inputs S12-S21.  Some of these inputs (S16, S18-21) are unwired, and their corresponding operations are 0, as expected, except for S16.  S16 is unwired, but S6 is 12, not 0.   So to correct this error, S6 should be changed from 12 to 0.  However, the outcome is the same whether or not this "error" is corrected, so DBDOC doesn't report it.

New in 10.7: Rung stack not initialized

There is also another problem, the second reported error, which is the one causing the unexpected [1] output:

Rung stack not initialized [ERROR 306]

Rung block Module 9,25,05 Block 7660 logic invalid because S3 is an OR operation[92505F2A.CAD]
This is a type of error newly detected in DBDOC 10.7.  It is capable of causing a significant system error.

How these rung blocks work is that each operation is carried out in order, and the result of each operation is placed on the stack.  The next operation is typically an AND or OR with the current input and whatever is on the stack (i.e. the result of the previous operation).

  1. In this case, the first operation is S2 (0) performed on input S12.  0 means use the value from the stack, i.e. ignore the actual input value S12.  As it happens, the uninitialized stack value is [1]!   But in any case S2 accomplishes nothing.
  2. The next operation is S3 (12) performed on input S13.  This means OR the input S13 with the value on top of the stack.  Well, the value on top of the stack is [1], so the result of this operation is always [1], regardless of whatever S13 is.  So this operation is also pointless.
  3. Similarly, S4 and S5 also OR their corresponding inputs with [1], yielding [1] on top of the stack.
  4. Finally, S7 is 11, which means AND the input ([1] in this case) with the top of the stack (current top of stack is guaranteed to be [1]), for an inevitable [1] final output, regardless of the values of S2-S5.
The basic problem here is that the stack was not initialized. The logic would make sense if S2 was 10 (PUT) instead of 0.  S2=10 would mean put the value of S12 ([0]) onto the stack.  Then the next operation, S3 (12), would OR [0] with the value of S13, yielding the value of S13, instead of a guaranteed [1].  

(Technically, S3 could be 10 (PUT) instead (if S2 was actually meant to be ignored), hence the error message complaining that S3 is OR.  And either S2 or S3 could also be an 11 (AND) with no change in result).

The important thing is that the stack needs to be initialized sensibly with a PUT (x0) or an AND (x1) before it is used, or there will be unexpected results. 

Enjoy these examples from real systems.  DBDOC Version 10.7 and beyond will detect this uninitialized stack problem if you happen to have it lurking in your system.

Some details for those not familiar with DBDOC:
  • Blue lines show a signal that carries the quality attribute.
  • A white box shows value [0] whereas a blue box shows value [1].
  • DBDOC presents the rung logic as a little ladder diagram.
  • The little "top hat" symbol means a change from [0] to [1], triggering a [1] for one cycle.
  • Specs can be moved in DBDOC to get them out of the way.
  • The warning triangle shape is an Error Marker, informing you of a DBDOC message.
  • The yellow box is a data tip telling you about the Error Marker.
These examples come from power plants in Delaware, Pennsylvania, Michigan and Wales. Where the logic was not used, the question can be asked if that was caused by inability to commission it.




















Thursday, February 11, 2016

50% of Systems Have Certain Function Blocks Unintentionally Disabled. Is Yours One of Them?

DBDOC is unique in giving you significant help in finding integrity issues in your system. Every INFI 90 system in the world will benefit from improving safety, reliability and operation with DBDOC's Integrity Plus approach. Our Error Browser and Error Marker development was designed to make it possible to manage errors and improve the integrity of your systems. 
 
In our most recent versions, we have added tests for three function blocks that are disabled by default.
  • FC 3 - Lead / Lag - S2 defaults to 0 disabling the function
  • FC 8 - Rate Limiter - S2 defaults to 0 disabling the function
  • FC 166 - Integrator - S4 defaults to 0 disabling the function
For a function block to be disabled by default is horrific. Only three of the 200 types or so are (the rest are enabled by default). The hapless users put function blocks in place, but they do nothing that they were intended to do, because they are disabled. Now and forever, they are booby-trapped.

What do you think? Can there be any justification for most function blocks being enabled by default, with only these three exceptions?

Am I wrong? Are there other booby-traps we have missed? Please let us know.

In my review of test data for 228 systems around the world, I found
  • Lead / Lag - 605 disabled in 83 systems
  • Rate Limiter - 392 disabled in 86 systems
  • Integrator - 50 disabled in 26 systems
In actuality, 75 systems had one of these; 42 systems had two and 8 hit the TriFecta! In total 125 of the 228 systems had one to three of these errors - 55% of them.

What about the "real world" - places where DBDOC checking has not been used yet? Here is what this test detected in a small power plant being worked on now by extremely competent people:
  • Module 1,02,02 Block 8507 FC8 disabled by spec values
  • Module 1,02,02 Block 9541 FC8 disabled by spec values
  • Module 1,02,02 Block 10295 FC8 disabled by spec values
  • Module 1,02,02 Block 11049 FC8 disabled by spec values
  • Module 1,02,02 Block 11803 FC8 disabled by spec values

 
Holy Rate Unlimiter, Batman! http://holysmokesbatman.com/directory contains 350 actual sayings, perhaps the best being "Holy Time Bomb".
 
The 5 errors out of 152 Rate Limiter blocks show that only DBDOC can protect you from these problems.
 
Here are examples of each from real systems.
 

The objective of this FC 3 Lead/Lag block is to apply a time constant of 60 seconds to changes in the PV as applied to the APID control algorithm. This is not happening here because, unbeknownst to (or unnoticed by) the DCS specialist, the block is disabled and feeds the input directly to the output.

 

The first Rate Limiter example looked like it was booby-trapped in the sense that sometime in the future an unsuspecting body would put meaningful values on the limits and expect them to work. As you can see here, the negative going rate limit of 0.00333 per second presumably is intended to prevent larger drops in the value from affecting the process. However, the block does not function.

 
 
 

In the case of the integrator, it is S4 that is the trap. Clearly, nobody puts an integrator and tag into a system not intending to get data. This one will not get data because S4 is not wired to a constant value 1.
 
Only DBDOC can improve your system integrity by detecting these relatively common oversights.
 


Saturday, June 20, 2015

How To Provide Remote DCS Support Without Compromising System Security

Critical DCS Support Aspects

There are times in the life of a DCS system that timely access to operating data is critical for maintenance of reliable operation. Sites have only a few DCS specialists, whose time is severely limited. Even the most critical systems do not have 24/7 resident specialists available.

INFI 90 Has Read-Only Access (via DBDOC)

INFI 90 systems are fortunate, because remote read-only access to live DCS data is possible by way of DBDOC. The DCS specialists can examine a plant situation in the most timely manner possible. They can respond faster, diagnose problems from anywhere and guide people at the plant through fault-finding and problem resolution immediately rather than adversely affecting the plant (and the public) with the delay time needed for them to get to the plant.

Read-only access protected by a VPN (Virtual Private Network) allows immediate plant support, increasing the reliability of the plant output, as well as its profitability and safety. Reliablility, profitability and safety gains - things worth working for.

How Safe is the Plant VPN?

Competent IT techniques protect access to salary, accounts payable, and accounts receivable data. All manner of plant technical and operating data is just as well protected. VPN technology is critical to the operation of companies.

What if somebody can see the data? DBDOC's read-only access guarantees that no changes can be made to the DCS.

Decrees About Access From Outside

Decrees have been made in some operations that there shall be no access to the plant data from outside the process network. On-site action is required to resolve problems, even if it takes the support personnel too long to get there to do the job. Valid performance requires far more people than are available or can reasonably be trained to the level needed.

 Should Prohibiting External Access be Reviewed?

It will take disasters caused by ill-considered decrees limiting access for support purposes to force the re-examination of such policies. More likely, fingers will be pointed at various people, none of them culpable.

DBDOC has created the ability to do immediate and effective read-only trouble-shooting remotely for INFI 90 systems. The people using DBDOC read-only access know that it helps them make their plants safer and more reliable.

Friday, December 20, 2013

The Art of DBDOC - Live Specs and NVRAM Failure

Summary

NVRAM failure can be a big problem.  Doing a DBDOC Live Loop Annotation fetching the block specifications will fail if the NVRAM has failed.  This could be useful information to you.

Details

A client reported that DBDOC Hyperview could not fetch the specs of a block.  In fact, the specs could not be fetched in any block in that module.  This is shown in this image.  Live data could be fetched - only the reporting of the specifications was affected.


However, fetching specs worked fine in other modules.  The example in a clone of the problem one, as you can see.


What could cause this problem? 

The next two images show the difference between working and failing module status fetches. 




Guess what?  The problem module shows NVRAM failure status: Fail.  The one that is working says: Good.

From the Client

"I believe a NVRAM failure will prevent looking at any of the configuration."

Subsequent Perspective

"The module will continue to operate with an NVRAM error because a copy of the configuration is held in SRAM and executes from there. The next time the module is reset it will not startup but will fail.

"This module had failed earlier and was hard initialized during an outage and did not show the errors, but has NVRAM failure now."

New INFI 90 "art" has been crafted.  This is the first time we know of that the module status fetch we created has been used to solve a problem.

Monitoring Exception Report Performance

Are Dated Design Compromises Affecting Your HMI and History Data Precision?

In many INFI 90 systems, there is a significant loss of continuity between the system implementation and its current use and performance.  The experts that made the original decisions are long gone, with no documentation and justification for many decisions that were made.

How can you find out if the system performance tuning decisions made are still valid?  Why is it possible that the way things were done years ago is no longer valid?  

Systems have gone from NET 90 to INFI 90 (plant loop to INFI loop).  Additionally, the PCU now has much higher communication performance available in the form of the NIS21/NPM22 pair.  The old hardware could only generate (in a PCU) 400 exception reports (XRs) per second, whereas the new hardware can do many times that number.

What are the ramifications for INFI 90 systems?  Can limitations decided on long ago be backed off? Are the decisions made long ago still valid now after you spent all that money on new communication modules?

Especially if you have PCUs with new NIS21/NPM22 communication modules, you are very likely to have the ability to generate much more fine-grained data for your HMI / consoles and for your history system, essentially for free.  The capability is there.  Why not use it?  If your system has older hardware, it may have been set up so conservatively that there is actually lots of capacity available you can avail yourself of, too.

Here is my humble sketch of how you would use spare blocks (hopefully) and a lightly loaded module to monitor the performance of your system from the perspective of timeliness or delay of exception reports.

1. In a Module to be Monitored, Create An Exception Report Generated Once Per Second

The first outrageous suggestion is that you generate an exception report from the seconds value in any module you wish to monitor.  The sketch shows this.






To be able to stop the exception reports, you would simply put a transfer block and an ON/OFF block between block 22 and S1 of the AO/L block.  This would allow you to turn on the exception reports only when you wished to check.  However, it is very difficult to imagine that adding one exception report per second per module will really make a significant difference.

You can see that, as 1 second is more than 1% of 100, an exception report will be generated every second. The objective of this logic is to use the added load for good benefit.  You will have the seconds value in Loop 1, PCU 10, Module 4 available as an exception report.

2. Create Your Time Standard in Lightly Loaded Safely Manipulable Module

The rest of the implementation uses a lightly loaded module that you can manipulate safely.  Since the objective of this work is to increase the precision of a lot of data in the system, you have to decide if the effort is worthwhile, of course.

In most systems, the time is synchronized around the loop.  Do you know it works for sure?  If it does not, you will find out when you go further.  The second bit of logic, in the lightly loaded module (Loop 1, PCU 5, Module 4 in the example), simply puts an Output Reference on the seconds value in that module.





You can see that the value on the OREF "10504 SECONDS" ought to be pretty close to any other SECONDS value in the whole system.

3. Create an Exception Report Import and Comparison Logic

All that is needed now is to import the seconds value from the module being monitored and compare it to the reference value in our lightly loaded module.  Probably 5 seconds for an alarm is horribly high, but normal monitoring techniques will tell you easily enough how tight you can get the test.  If you define the tag "11004 SECONDS LAG" (or "11004_SECONDS_LAG"), you can get an alarm whenever the exception report is delayed (or simply log it).




Of course, your imagination is the limit.  You can send the difference to an AO/L block and monitor that using your historian.  You can filter and average and remove jitter if that is needed.  The sky's the limit!

Note how easily you could monitor all the modules this way that are purported to be heavily loaded.  The only significant work involves the lightly loaded module that you can manipulate safely.

4. Ramifications for Improved HMI and History Data

What happens if you find that there is no delay?  You also might have implemented the technique in the post "Monitoring Node Communication CPU Load" and found that your node CPU usage is very minimal.

The most important limitation in existing INFI 90 systems is the Significant Change specification.  This number tells either a percent of span (AO/L blocks, Station blocks) or an actual EGU value (FC 177, 222, 223) that triggers a new exception report.  Traditionally, 1% is the default value used to try to keep the load managed.  Is this still valid, if you have no exception report generation delay and idle communication modules?

If you have proven that you have excess communication capacity, you can start improving (reducing) the significant change specifications of important or too coarse tags to get better data to the operators, engineers and executives.  You can be sure that you have lots of capacity by keeping the CPU load reasonable (but higher than the minimal level found in many modern systems).  You have a direct test and warning if you are getting delays in the generation of exception reports.

5. Negative Ramifications of Current INFI 90 Practice with respect to Significant Change

In case you wonder, or have to justify even thinking about the monitoring suggested here, you will want to look closely at my post Improved Tag and History Data Precision in INFI 90 Systems.  It will give you "grist for the mill" as you try to make the data originating in your system better.  It will show you that there usually is a lot of room for significant improvement.

DBDOC and Spare Blocks

Sometimes, you have to find a spare block and the spare blocks / boneyard sheets have not been maintained.   DBDOC can make this task systematic and as easy as possible. We plan to add a feature one day to directly identify unused blocks, which will be even nicer.  Keep those cards and letters coming, folks!

Start with the Table of Contents - Miscellaneous Indices chapter.  Click on Function Codes.  In the Index to all Function Codes, click on the Function Code 30 entry to get to the list of all FC 30 blocks in your system.


You are now at a list of all the FC 30 blocks in the system.  Scroll down the list until you get to the module you want, in this case, Loop 11, PCU 10, Module 2 (Module 11,10,02 in DBDOC terms) and click on the highlighted entry to call up that block.  You will see the block in the CLD or CAD sheet, usually with a line showing it is (probably) used.  If you turn on "attributes" with the "A" key, you will see if the block has a tag. You should, at least for a start, assume that it is used if it has a tag or if it has an output reference.

The example shows that the first block is tagged "1-TI-2241" and that it has a line carrying its value someplace to boot.  Probably used, eh?


Now you simply walk through the FC 30 blocks with the "L" key ("shift L" to go up).  The same functionality is given by  andin the icons.

When you get to one that has no line and no tag, you have found a candidate spare block.


Clicking on the block number (1501) brings up the index of all the places in the world where this block is purported to be used, hopefully only its source right here.  This one certainly seems to be unused.


It makes sense to be satisfied that you have a good enough DBDOC build that you can count on the fact the block is not used.  For example, it is possible that it is imported by some other project, and you did not build all the projects together in your DBDOC build.  If that could be the case, you should do further analysis.

However, no other tools can get you this far this fast.  We are always ready to help you be sure you have a good DBDOC build that resolves everything.  You have a candidate spare block and it really did not take very long.

What do you do if you walk right through Module 11,10,02 without finding a spare?  You can go back through the blocks and click on the output block number, looking for blocks that are not used in any graphics.  Although these might be in your history system, you can go after that usage and perhaps find that the block can be re-purposed with no problem.


When you are walking through the blocks checking for how they are used, the key sequence is easy enough to do semi-automatically:
  • click on output block number
  • back-space to get back to the function code index
  • type "L" (or "l") to get to the next linked block and repeat
There are, of course, other ways to do this.  It is very nice when all spare blocks get put into boneyard pages.  However, that is not always the case.  When you have to find one and see how it is used or not, this DBDOC technique will certainly help you.