Showing posts with label PGP graphics. Show all posts
Showing posts with label PGP graphics. Show all posts

Friday, March 1, 2024

Puzzles in Symphony Plus

To mark my return to blogging about DBDOC and INFI 90, I pose some puzzles.

FC 116 - Jump/Master Control Relay

I have always been curious about this function code. It is able to "jump" over block processing and

  1. and leave the skipped blocks unchanged S3= 0
  2. or zero the skipped non-forced rung blocks that are jumped S3= 1
We have data from 600 active and prospective DBDOC builds over the years. Fewer than 5% of these INFI 90 had this function block. Furthermore, many that had it at some time in the past no longer use it.

The block appears to still be supported in SPlus Engineering.

Can anybody add insight to the current thinking about FC 116?

UCB and SPO/PGP Graphics

Once upon a time, SPO SPlus Operations graphics were PGP and used files with extensions .UCBG, .UCBV and so on. This continued into SPO, where the WORK folders used them.

It is obvious that the UCB initials meant something. Can anybody indicate what those letters stood for?

Chaining of FC 126 RDEMUX Blocks

We find numerous FC 126 blocks that have the value of S3 "Block address of next block in link list" incorrect. Here is an example:




Is this an issue? Is it not an issue because the chained RDEMUX block is not used? Are there ramifications that are not apparent from the documentation?

In DBDOC builds, the error codes [316] through [319] and [325] are have the attributes that they report things that violate the rules, but we do not know if they actually cause a problem other than not actually working. If the result is not used, who cares? 

What I could check had the badly linked blocks unused generally. The puzzle is if this ever is worth reporting.



Tuesday, December 5, 2023

DBDOC 11.4 is available now!

DBDOC 11.4 features important new capabilities, particularly in terms of system support.  We see the first support for ABB SPE 2.4, as well as the first implementation of AC 800M support (alone, or in a mixed INFI 90 / AC 800M system).  In addition, there are significant improvements to support for 800xA and PGP graphics, as well as numerous bug fixes and improvements to Hyperview and the rest of the applications. 

Download DBDOC 11.4 Here

Powerful new support for SPE 2.4 systems. 

  • DBDOC now supports S+ Engineering 2.4 systems. 

Initial support for AC 800M systems. 

  • DBDOC now supports mixed INFI 90 / AC 800M and exclusively AC 800M systems. 
  • Full navigational and search support is implemented. 
  • Click to see all uses of a function block, and double-click to go to its location in the configuration.
  • Multipage sequence diagrams are automatically merged for easy visualization and navigation. 

Improved support for 800xA graphics 

  • BBA folders as well as ASSYST folders now searched by the build system. 
  • Improvements to hotspot generation, placement, and sizing. 
  • Improvements to dynamic bar support, and identification of more horizontal dynamic bars. 
  • Text handling improved to make search more correct and complete. 

Improved support for SPlus graphics 

  • Improved handling of SPO 3.3 .mimic & .bin files 
  • Many improvements to hotspot, link, and text generation and placement. 

Multi-user BuildPlus buildroots 

  • BuildPlus should now automatically and seamlessly handle multiple users, even of different privilege levels, seeing the same buildroots. 

Hyperview in a Web Browser 

  • Various and sundry bug fixes and improvements to functionality and usability.
  • More browsing and navigation idioms supported, such as browse and synch to table of contents. 
  • All dbdoc file “documents” can be accessed transparently via a regular web browser url. 

Search 

  • Recall search results with “R” key 
  • The database of a search result is now displayed in database search results. 
  • Title searches are now retained after restart, for convenience. 

Hyperview miscellaneous 

  • Due to popular demand, Treeview Table of Contents has been fully reinstated. 
  • Double click on a signal line on CAD/CLD goes to block source. 

Live data 

  • Blue “EXTERNAL” is no longer  shown for unfetchable live data on graphics. 
  • Stop fetching data for a block if Destination Node Offline error is received.