DBDOC: Reads the Manual and Checks Your Specs.

DBDOC is unique in giving you significant help in finding integrity issues in your system. Every INFI 90 system in the world would benefit from improving operational safety and reliability. Our Error Browser and Error Marker development was designed to make it possible to manage errors and improve the integrity of your systems.

Here you see our much loved copy of the function code manual, dog-eared and duct-taped. You've probably read it too, but possibly not as intensely as we have.

Based on studying the documentation and the experiences of our clients, we added new tests for function block specifications that violate the documentation in ways that seem significant. Read on to see what we found.

We reviewed test data for 229 systems around the world, and found 1160 new errors of note in 77 systems involving 33 function codes - 15 errors per system. Of course, this means that 68% of the systems had none of the specification errors we looked for. It also means that over 1/3 of the systems had these new errors Composer did not find, but that DBDOC will.

I expect this will be the most boring blog I ever write. Holy Understatements, Batman!

Here are example of errors found in various specification values for various function codes from real systems. Some could bite!  All are now reported by DBDOC in the Error Browser.

FC35 - 45 instances in 21 systems
  • Module 5,65,02 Block 133 FC35 S2 value 005 is out of the valid range [000,102]
FC36 - 15 instances in 4 systems
  • Module 5,26,05 Block 6441 FC36 S9 value 9 is out of the valid range [0,8]
  • Module 7,101,06 Block 5800 FC36 S10 value -1 is out of the valid range [0,1]
FC45 - 22 instances in 6 systems
  • Module 2,48,02 Block 854 FC45 S2 value 20 is out of the valid range [0,2]
FC50 - 1 instance in 1 system
  • Module 3,01,04 Block 4082 FC50 S1 value -1 is out of the valid range [0,1]
FC69 - 9 instances in 4 systems
  • Module 32,04,05 Block 3285 FC69 S2 value 5 is out of the valid range [0,2]
FC80 - 61 instances in 26 systems
  • Module 2,78,02 Block 2151 FC80 S6 value 39 is out of the valid range [1-3 or 5-8]
  • Module 2,15,05 Block 2039 FC80 S17 value 246 is out of the valid range [0,7]
  • Module 1,11,02 Block 2494 FC80 S23 value 5 is out of the valid range [0,4]
FC82 - 4 instances in 3 systems
  • Module 3,02,20 Block 1992 FC82 S5 value 30 is out of the valid range [0,2]
  • Module 2,12,06 Block 15 FC82 S15 value 179 is out of the valid range [0,1]
FC83 - 501 instances in 4 systems
  • Module 11,30,15 Block 463 FC83 S1 value 65 is out of the valid range [0,63]
FC84 - 5 instances in 4 systems
  • Module 2,20,02 Block 6641 FC84 S2 value 10 is out of the valid range [0,1]
  • Module 2,20,02 Block 6641 FC84 S2 value 10 is out of the valid range [0,1]
FC86 - 1 instance in 1 system
  • Module 2,104,10 Block 1882 FC86 S6 value 013 is out of the valid range [000,101]
FC95 - 36 instances in 5 systems
  • Module 1,62,03 Block 979 FC95 S7 value 2 is out of the valid range [0,1]
  • Module 1,53,02 Block 9062 FC95 S12 value 7 is out of the valid range [0,1]
FC110, FC111, FC112 - 24 instances in 10 systems
  • Module 5,12,04 Block 4015 FC110 S1 value 20 is out of the valid range [0,3]
  • Module 5,23,02 Block 56 FC111 S1 value 10 is out of the valid range [0,3]
  • Module 7,09,03 Block 4140 FC112 S1 value 10 is out of the valid range [0,3]
FC123 - 12 instances in 1 system
  • Module 4,07,06 Block 3793 FC123 S7 value 22 is out of the valid range [0,11]
  • Module 4,07,06 Block 3793 FC123 S8 value 22 is out of the valid range [0,11]
FC124 - 6 instances in 2 systems
  • Module 5,33,03 Block 3194 FC124 S11 value 120 is out of the valid range [00,22]
  • Module 5,33,03 Block 3194 FC124 S13 value 60 is out of the valid range [00,22]
FC126 - 3 instances in 1 system
  • Module 1,14,11 Block 8501 FC126 S2 value 115 is out of the valid range [0,2]
FC129 - 92 instances in 33 systems
  • Module 1,15,02 Block 3405 FC129 S7 value 003 is out of the valid range [000,111]
  • Module 1,15,06 Block 3133 FC129 S8 value 1000 is out of the valid range [000,111]
  • Module 1,20,05 Block 7810 FC129 S9 value 002 is out of the valid range [000,111]
  • Module 1,23,03 Block 3995 FC129 S10 value 1000 is out of the valid range [000,111]
  • Module 5,15,04 Block 2559 FC129 S11 value 20002 is out of the valid range [0000,2222]
  • Module 1,44,04 Block 2509 FC129 S13 value 0003 is out of the valid range [0000,2222]
  • Module 1,24,03 Block 1808 FC129 S14 value 222 is out of the valid range [000,142]
  • Module 1,04,03 Block 3993 FC129 S15 value 23 is out of the valid range [0,1]
  • Module 3,54,04 Block 7764 FC129 S19 value 5 is out of the valid range [Any or All of 0,1,2,3]
FC132 - 64 instances in 14 systems
  • Module 1,01,15 Block 1346 FC132 S3 value 2 is out of the valid range [0,1]
  • Module 1,60,02 Block 448 FC132 S3 value 4 is out of the valid range [0,1]
  • Module 11,26,04 Block 1106 FC132 S3 value 7 is out of the valid range [0,1]
  • Module 34,46,03 Block 8150 FC132 S10 value 78 is out of the valid range [0,5]
  • Module 1,03,04 Block 1211 FC132 S13 value 50 is out of the valid range [0,5]
  • Module 2,01,02 Block 244 FC132 S16 value 150 is out of the valid range [0,5]
FC136 - 28 instances in 3 systems
  • Module 1,07,03 Block 1258 FC136 S16 value 3.0 is out of the valid range [0.0, 1.0, 2.0]
FC140 - 34 instances in 4 systems
  • Module 10,02,07 Block 1076 FC140 S4 value 8078 is out of the valid range [00,11]
  • Module 7,103,02 Block 3250 FC140 S5 value 212 is out of the valid range [0,63]
FC143 - 1 instance in 1 system
  • Module 1,20,09 Block 8872 FC143 S1 value 3 is out of the valid range [0,2]
FC149 - 60 instances in 10 systems
  • Module 5,41,02 Block 232 FC149 S3 value 8 is out of the valid range [0,1]
  • Module 11,01,04 Block 161 FC149 S11 value 5 is out of the valid range [0,2]
  • Module 11,01,04 Block 161 FC149 S12 value 5 is out of the valid range [0,2]
  • Module 11,01,04 Block 161 FC149 S13 value 5 is out of the valid range [0,2]
  • Module 11,01,04 Block 161 FC149 S14 value 5 is out of the valid range [0,2]
  • Module 11,01,04 Block 161 FC149 S15 value 5 is out of the valid range [0,2]
  • Module 11,01,04 Block 161 FC149 S16 value 5 is out of the valid range [0,2]
  • Module 11,01,04 Block 161 FC149 S17 value 5 is out of the valid range [0,2]
FC151 - 6 instances in 3 systems
  • Module 1,65,05 Block 4531 FC151 S6 value 4532.0 is out of the valid range [0.0,127.0]
  • Module 2,30,03 Block 7180 FC151 S7 value 3 is out of the valid range [0,1]
FC156 - 5 instances in 4 systems
Module 1,18,03 Block 6438 FC156 S19 value 32 is out of the valid range [0,1]
  • Module 3,03,02 Block 7284 FC156 S20 value 40 is out of the valid range [0,1]
  • FC166 - 8 instances in 3 systems
Module 4,05,07 Block 3697 FC166 S2 value 120 is out of the valid range [0,2]
  • Module 3,01,04 Block 3807 FC166 S8 value 32767 is out of the valid range [0,1]
  • FC182 - 19 instances in 1 system
  • Module 1,07,14 Block 56 FC182 S1 value 000 is out of the valid range [001-009, 020-124, 040-041, 064]
FC190 - 6 instances in 3 systems
  • Module 2,32,07 Block 2280 FC190 S2 value 7200 is out of the valid range [1,6553]
FC216 - 61 instances in 10 systems
  • Module 1,09,07 Block 8172 FC216 S3 value 19 is out of the valid range [1,16]
  • Module 20,38,07 Block 650 FC216 S4 value 051 is out of the valid range [000-109, 010-113, 020-125, 040-144, 060-161, 099-199]
  • Module 1,03,04 Block 1428 FC216 S5 value 2 is out of the valid range [0,1]
  • Module 6,60,08 Block 162 FC216 S11 value 0 is out of the valid range [16,24]
FC222 - 1 instance in 1 system
  • Module 1,09,02 Block 1023 FC222 S2 value 1022 is out of the valid range [0000-1209, 0010-1115, 0210-1214, 0300-1302, 0400-1400, 0500-1500, 0900-1900]
FC224 - 18 instances in 4 systems
  • Module 1,09,02 Block 1048 FC224 S2 value 1047 is out of the valid range [0,2]
  • Module 1,09,02 Block 1048 FC224 S3 value 1046 is out of the valid range [0,255]
FC226 - 8 instances in 2 systems
  • Module 20,10,31 Block 8358 FC226 S3 value 10 is out of the valid range [0,4]
FC247 - 4 instances in 2 systems
  • Module 1,13,04 Block 953 FC247 S5 value 5 is out of the valid range [1-4 or 6-8]
Holy Complications, Batman! A number of expressions in http://holysmokesbatman.com/directory apply. DBDOC helps improve your system's integrity.


Wednesday, August 3, 2016

Output Cusps - Exceptionally Artistic!

We came across the pretty but alarming output forms shown here at a client. The scale is one minute per cusp and just over 1% amplitude. This is important because it means that the HMI and historian would not see this at all. DBDOC Watch Window handles it nicely, as is evident.

So what is going on here?



The blue line is the output of a FC 80 Station block and the output cusps were, in fact, a significant issue. The green line is the raw PV input (nice and smooth). However, the APID block was being fed by an exception-reported version of the PV, shown in red. The significant change specification was 0.1%, so the exception-reported value actually was competently implemented, changing in steps, as expected.

The problem simply is that the APID algorithm used a derivative term. As the two diagrams make painfully obvious, this simply does not work. Although the PV signal is changing at a nice fairly constant rate, the controller, fed by the red step input, is hit with a huge change accumulated over one minute, but seen as happening in 250 ms. Thus, the derivative is calculated as being 240 times bigger than it actually is.






















The second image shows that, if the PV is changing so that the exception reports are triggered by the significant change, the cusps are smaller, as they have a better time base. but they are still misleading and problematic.

The bottom line is that PID and APID algorithms should never use a derivative term if the PV is affected by an exception-reported input PV. It cannot work mathematically, and it sure kicks the process in the teeth, again and again.

DBDOC can't yet detect this error situation automatically, but we are working on it.  Stay tuned.

DBDOC 10.7: Now Detects Unitialized Rung Stacks

We always have our eyes out for new error situations that DBDOC can detect and protect you from.

At a training session recently, we happened to notice a FC 111 rung block with mysterious output [1] (blue). This made no sense, because the logic is OUTPUT = (S13 OR S14 OR S15 OR S16) AND S17, but none of S13-16 are [1] (blue), so the output shouldn't be [1], but it is. We verified the specifications, which matched what the CLD showed.



There are actually two different reported errors on this particular block, as you can see from the presence of two error markers.  There is also an unreported error, which we will describe for completeness.

Rung block spec is wired but unused

The first (reported) error is reported as follows:

Rung block spec is wired but unused [ERROR 124]

Rung block Module 9,25,05 Block 7660 S12 is wired (block 3006) but unused by S2 value 000[92505F2A.CAD]
S2 is the operation that acts on input S12, but S2 is 0, which means ignore the input, and instead use the value from the top of the stack.  It may well be unintentional that S2's value be ignored.

Operation on an unwired input

There is actually another error which is not reported, because it makes no difference to the output:

The specs S2-S11 are operations on inputs S12-S21.  Some of these inputs (S16, S18-21) are unwired, and their corresponding operations are 0, as expected, except for S16.  S16 is unwired, but S6 is 12, not 0.   So to correct this error, S6 should be changed from 12 to 0.  However, the outcome is the same whether or not this "error" is corrected, so DBDOC doesn't report it.

New in 10.7: Rung stack not initialized

There is also another problem, the second reported error, which is the one causing the unexpected [1] output:

Rung stack not initialized [ERROR 306]

Rung block Module 9,25,05 Block 7660 logic invalid because S3 is an OR operation[92505F2A.CAD]
This is a type of error newly detected in DBDOC 10.7.  It is capable of causing a significant system error.

How these rung blocks work is that each operation is carried out in order, and the result of each operation is placed on the stack.  The next operation is typically an AND or OR with the current input and whatever is on the stack (i.e. the result of the previous operation).

  1. In this case, the first operation is S2 (0) performed on input S12.  0 means use the value from the stack, i.e. ignore the actual input value S12.  As it happens, the uninitialized stack value is [1]!   But in any case S2 accomplishes nothing.
  2. The next operation is S3 (12) performed on input S13.  This means OR the input S13 with the value on top of the stack.  Well, the value on top of the stack is [1], so the result of this operation is always [1], regardless of whatever S13 is.  So this operation is also pointless.
  3. Similarly, S4 and S5 also OR their corresponding inputs with [1], yielding [1] on top of the stack.
  4. Finally, S7 is 11, which means AND the input ([1] in this case) with the top of the stack (current top of stack is guaranteed to be [1]), for an inevitable [1] final output, regardless of the values of S2-S5.
The basic problem here is that the stack was not initialized. The logic would make sense if S2 was 10 (PUT) instead of 0.  S2=10 would mean put the value of S12 ([0]) onto the stack.  Then the next operation, S3 (12), would OR [0] with the value of S13, yielding the value of S13, instead of a guaranteed [1].  

(Technically, S3 could be 10 (PUT) instead (if S2 was actually meant to be ignored), hence the error message complaining that S3 is OR.  And either S2 or S3 could also be an 11 (AND) with no change in result).

The important thing is that the stack needs to be initialized sensibly with a PUT (x0) or an AND (x1) before it is used, or there will be unexpected results. 

Enjoy these examples from real systems.  DBDOC Version 10.7 and beyond will detect this uninitialized stack problem if you happen to have it lurking in your system.

Some details for those not familiar with DBDOC:
  • Blue lines show a signal that carries the quality attribute.
  • A white box shows value [0] whereas a blue box shows value [1].
  • DBDOC presents the rung logic as a little ladder diagram.
  • The little "top hat" symbol means a change from [0] to [1], triggering a [1] for one cycle.
  • Specs can be moved in DBDOC to get them out of the way.
  • The warning triangle shape is an Error Marker, informing you of a DBDOC message.
  • The yellow box is a data tip telling you about the Error Marker.
These examples come from power plants in Delaware, Pennsylvania, Michigan and Wales. Where the logic was not used, the question can be asked if that was caused by inability to commission it.




















Friday, July 29, 2016

800xA Version 6.0 Now Supported

I'll keep this short and sweet: our ASSYST-made extraction tools for 800xA PG2 graphics have been updated to include support for version 6.0, and I've updated our frontend launcher to support the new programs. You can download the installer from our website where you can also find instructions for building 800xA graphics into a BuildPlus project, and of course you can always contact us if you have any questions or issues.

Tuesday, February 23, 2016

Light Rung Humor

These examples are taken from current projects being engineered at this time. I offer them for amusement and comment. You can decide if they are good engineering or not.

First some prototype logic that works, but might not be termed "nice". The block will serve as a 5-input OR block, but the second input is wired, not the first. It works. It is also booby-trapped, as proven by how this logic was cleaned up in the same project.



Next (below), you can see how that logic got cleaned up. Not nice at all, eh? The output is always Boolean 0 and the input on S8 is always ignored.

Why did  this client not get burned? DBDOC gives a message when the input on S8 is not being used, as is the case here. Note also that only DBDOC shows the ladder logic diagram based on what is there. Close call for this client, but no harm done. 



Finally, where it was done nicely in a different system. It is absolutely natural and works. The unused specifications have been cleaned up correctly.



You might ask why leave the rung block in there at all? Good question. It allows for changes to be made later to add more conditions. I do not know if people get paid by the block, but that would also justify it. Also, why clean up the specifications. In the ugly case, it changed working logic into non-working. Left alone, any additional inputs would be OR'd in as expected.

If this were your system, would you insist on S7 being used for the first input? Would you let the specifications be changed to make it work?

Funny? What do you think? What would you accept?

Thursday, February 11, 2016

50% of Systems Have Certain Function Blocks Unintentionally Disabled. Is Yours One of Them?

DBDOC is unique in giving you significant help in finding integrity issues in your system. Every INFI 90 system in the world will benefit from improving safety, reliability and operation with DBDOC's Integrity Plus approach. Our Error Browser and Error Marker development was designed to make it possible to manage errors and improve the integrity of your systems. 
 
In our most recent versions, we have added tests for three function blocks that are disabled by default.
  • FC 3 - Lead / Lag - S2 defaults to 0 disabling the function
  • FC 8 - Rate Limiter - S2 defaults to 0 disabling the function
  • FC 166 - Integrator - S4 defaults to 0 disabling the function
For a function block to be disabled by default is horrific. Only three of the 200 types or so are (the rest are enabled by default). The hapless users put function blocks in place, but they do nothing that they were intended to do, because they are disabled. Now and forever, they are booby-trapped.

What do you think? Can there be any justification for most function blocks being enabled by default, with only these three exceptions?

Am I wrong? Are there other booby-traps we have missed? Please let us know.

In my review of test data for 228 systems around the world, I found
  • Lead / Lag - 605 disabled in 83 systems
  • Rate Limiter - 392 disabled in 86 systems
  • Integrator - 50 disabled in 26 systems
In actuality, 75 systems had one of these; 42 systems had two and 8 hit the TriFecta! In total 125 of the 228 systems had one to three of these errors - 55% of them.

What about the "real world" - places where DBDOC checking has not been used yet? Here is what this test detected in a small power plant being worked on now by extremely competent people:
  • Module 1,02,02 Block 8507 FC8 disabled by spec values
  • Module 1,02,02 Block 9541 FC8 disabled by spec values
  • Module 1,02,02 Block 10295 FC8 disabled by spec values
  • Module 1,02,02 Block 11049 FC8 disabled by spec values
  • Module 1,02,02 Block 11803 FC8 disabled by spec values

 
Holy Rate Unlimiter, Batman! http://holysmokesbatman.com/directory contains 350 actual sayings, perhaps the best being "Holy Time Bomb".
 
The 5 errors out of 152 Rate Limiter blocks show that only DBDOC can protect you from these problems.
 
Here are examples of each from real systems.
 

The objective of this FC 3 Lead/Lag block is to apply a time constant of 60 seconds to changes in the PV as applied to the APID control algorithm. This is not happening here because, unbeknownst to (or unnoticed by) the DCS specialist, the block is disabled and feeds the input directly to the output.

 

The first Rate Limiter example looked like it was booby-trapped in the sense that sometime in the future an unsuspecting body would put meaningful values on the limits and expect them to work. As you can see here, the negative going rate limit of 0.00333 per second presumably is intended to prevent larger drops in the value from affecting the process. However, the block does not function.

 
 
 

In the case of the integrator, it is S4 that is the trap. Clearly, nobody puts an integrator and tag into a system not intending to get data. This one will not get data because S4 is not wired to a constant value 1.
 
Only DBDOC can improve your system integrity by detecting these relatively common oversights.
 


Friday, February 5, 2016

System Integrity — DBDOC Detects Bad TSTALM Blocks

DBDOC is unique in giving you significant help in finding integrity issues in your system. Every INFI 90 system in the world will benefit from improving safety, reliability and operation with DBDOC's Integrity Plus approach. Our Error Browser and Error Marker development was designed to make it possible to manage errors and improve the integrity of your systems.
 
In August 2014, we showed examples of detectable TSTALM errors from one system, but we continue to find this error being made. We have been reporting it for a decade, since 2006. DBDOC is the only valid way to identify this problem.
 
We report Function Code 69 TSTALM blocks that test the same block and mode. This usually happens when a TSTALM block is copied without S1 the specification that tells what block is being tested being made to match the new block numbers. Any of these TSTALM problems could have an adverse affect on a plant.
 
I did a review of test data for 228 systems around the world:
  • 22 had no TSTALM blocks - basically small systems averaging 1219 sheets each.
  • 206 systems had 3 or more - average size was 4022 sheets.
  • 90 had from one to 111 multiple TSTALM messages - average 8.2 errors.

The three systems with the largest number of messages looked like this:
  • 111 errors - 114 actions missed, 114 actions falsely triggered
  • 100 errors - 10 actions missed, 10 actions falsely triggered, 96 duplications
  • 84 errors - 84 actions missed, 84 actions falsely triggered
 
Holy Crossfire, Batman! This is from http://holysmokesbatman.com/directory.
 
The problem is that good logic gets cloned to do the same job again and again. The block numbers get changed and the changes compile cleanly. However, S1 must be changed when the logic is cloned in the same module, because the cloned value of S1 is guaranteed to be the only block in the module that is wrong. The failure to do this is not caught by Composer or WinCAD compilers, so the error does not get corrected.
 
Let's start with an example. Here is our message, as shown in Error Browser, with the good stuff circled in green:
 
 
 
Block 2614 is clearly expected to be asserted when block 2609 is put into Auto mode.
 
DBDOC shows you the block index for block 2609, which you see here with the green highlight for the intended and correct logic.
 
 
 
  
What do you make of the purple, red and blue highlighted references? Click on each of them to go to the TSTALM block that is strangely testing block 2609.
 
 
 
 
 
S1 of block 2115 (purple) obviously should be 2111, not 2609.
S1 of block 2365 (red) obviously should be 2361, not 2609.
S1 of block 2490 (blue) obviously should be 2486, not 2609.
 
Count the errors:
  • Blocks 2116, 2366 and 2491 will be asserted when MSDVDR block 2609 goes into automatic mode - three errors.
  • Blocks 2116, 2366 and 2491 will NOT be asserted when MSDVDR blocks 2111, 2361 and 2480 respectively go into automatic mode - three more errors
 
Six errors for the price of one! Good value from DBDOC, eh?
 
Composer should be made to set the value of S1 to -1 when a TSTALM FC 69 block is placed on a page. The illegal value should force the user to enter one that would work.
 
Note also that the warning triangles (Error Markers) are in front of you when you get to the dysfunctional logic, so you can see right away that there is possibly a problem. The two messages they show are:
 
Tested block on different page (which should be a clue), and
TSTALM block tests subsequent block, which means they are out of natural sequence.
 
I have found as many as seven such duplications (that is, 14 errors) that came from the cloning of a single set of functioning blocks. Clearly, this error can be made and missed. DBDOC can find it for you.
 
When you review these using DBDOC Error Browser, you simply hide any that are of no consequence. You flag ones like this that affect the process. When they are fixed, they will disappear from the diagnostics. If you create such an error, it will show up as a new error, highlighted in yellow.
 
DBDOC helps improve your system integrity.